ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
102 NSF (9.5 NSM)
Wall Finish
GYP. BOARD(SC)
AC Load Lights
1.0 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
1.0 W/SF
8'-0" (2.66 METERS) Base
Ceiling Height
Number of People
1
6" (152 mm) INTEGRAL
Floor Load
-
COVE BASE
Noise Criteria
NC-40
Room Pressure
NEGATIVE
WSF
Floor finish
Note:
Dry Bulb Temp Cooling Range
78F (25C)
Lead Lining
-
Refer to PG-18-1 and PG-18-6
72F (22C)
Minimum Air Changes per Hour
SEE NOTE *
Minimum % Outside Air
100
YES
Special Exhaust
-
Steam
-
ELECTRICAL
Relative Humidity
50 %
Relative Humidity
30 %
Lighting
Power
General
20 FC, 1.0 W/SF
General
720 W
NOTE:
Special
-
Special
-
*INDEPENDENT EXHAUST, MINIMUM 1.0 CFM/SF,
Emergency
Emergency
-
ALL FIXTURES
BUT NOT LESS THAN 50 CFM
PLUMBING AND MEDICAL GASES
-
Medical Air
Cold Water
-
Medical Vacuum
Hot Water
-
-
Oxygen
-
Sanitary Drain
-
Nitrous Oxide
-
Acid Waste
-
-
Silver Recovery
-
TELECOMMUNICATIONS
Anesthesia Evac
-
Patient Monitor
Telephone
-
-
-
-
Nurse Call
Intercom
Code One
-
Public Addr.
-
-
CCTV
ADP
-
SPECIAL EQUIPMENT
Radio
-
IF REQUIRED, HAZARDOUS/EXPLOSIONPROOF
ROOM CONSTRUCTION TO COMPLY WITH
NFPA 99, CHAPTERS 4, 5, 9 AND ELECTRICAL
CONSTRUCTION REQUIREMENTS OF NFPA 70.
Design Guide - Surgical Service
Design Standards
Gas Cylinder Storage Room
Guide Plate:
7-2b
102 NSF (9.5 NSM)
Date: August 2005