HEATING, VENTILATING AND AIR CONDITIONING
ARCHITECTURAL
Floor Area
150 NSF (14.0 NSM)
Wall Finish
GYP. BOARD
AC Load Lights
2.5 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
3.0 W/SF
Base
8'-0" (2.66 METERS)
6" (152 mm) INTEGRAL
Ceiling Height
Number of People
2
Floor Load
100 PSF
COVE BASE
Noise Criteria
NC-40
Room Pressure
(0)
Floor finish
WSF
Note:
Lead Lining
-
78F (25C)
Dry Bulb Temp Cooling Range
Refer to PG-18-1 and PG-18-6
72F (22C)
Minimum Air Changes per Hour
-
Minimum % Outside Air
100
YES
ELECTRICAL
-
Steam
-
Lighting
Power
Relative Humidity
50 %
Relative Humidity
30 %
General
70 FC, 2.0 W/SF*
General
1440 W**
Special
UNDERCOUNTER
Special
-
Emergency
Emergency
ALL
ALL
PLUMBING AND MEDICAL GASES
-
-
Cold Water
Medical Air
-
Medical Vacuum -
Hot Water
Sanitary Drain
-
Oxygen
-
-
Acid Waste
Nitrous Oxide
-
Silver Recovery
-
-
TELECOMMUNICATIONS
Anesthesia Evac MED GAS
AREA ALARM
Patient Monitor
-
Telephone
YES
DUTY STATION*
PART OF TELEPHONE
Nurse Call
Intercom
Code One
-
Public Add.
-
-
CCTV
ADP
-
SPECIAL EQUIPMENT
Radio
-
*CONNECTED TO RECOVERY
None
Design Guide - Surgical Service
Design Standards
Control and
Guide Plate:
7-1b
150 NSF (14.0 NSM)
Date: August 2005