ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
200 NSF (18.6 NSM) Wall Finish
GYP. BOARD(SC)
AC Load Lights
1.5 W/SF
-
Ceiling
GYP. BOARD(SC)
Wainscot
AC Load Equipment
2.5 W/SF
9'-0" (2.75 METERS) Base
6" (152 mm) INTEGRAL
Ceiling Height
Number of People
2
COVE BASE
Floor Load
100 PSF
Noise Criteria
NC-40
Floor finish
WSF
Room Pressure
POSITIVE
Note:
Dry Bulb Temp Cooling Range
78F (25C)
Refer to PG-18-1 and PG-18-6
Lead Lining
-
72F (22C)
Minimum Air Changes per Hour
8(SA)
Minimum % Outside Air
100
YES
ELECTRICAL
-
Steam
-
Lighting
Power
Relative Humidity
50 %
Relative Humidity
30 %
General
30 FC, 1.5 W/SF
General
1980 W
Special
-
Special
*
Emergency
-
Emergency
-
*(1) STRIP MOLD WITH DUPLEX RECEPTACLES 24" OC ABOVE COUNTER
PLUMBING AND MEDICAL GASES
YES
-
Cold Water
Medical Air
YES
-
Hot Water
Medical Vacuum
Sanitary Drain
YES
Oxygen
-
-
Acid Waste
Nitrous Oxide
-
Silver Recovery
-
-
TELECOMMUNICATIONS
Anesthesia Evac
-
Patient Monitor
Telephone
YES
-
-
-
Nurse Call
Intercom
Code One
-
Public Address
-
SPECIAL EQUIPMENT
-
CCTV
ADP
-
Radio
-
None
Design Guide - Surgical Service
Design Standards
Instrument Preparation and
Guide Plate:
6-2b
Storage Room
200 NSF (18.6 NSM)
Date: August 2005