ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
95 NSF (8.8 NSM) Wall Finish
GYP. BOARD(SC)
AC Load Lights
2.5 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
3.0 W/SF+VS-122*
Base
AS REQUIRED
Ceiling Height
6" (152 mm) INTEGRAL
Number of People
1
COVE BASE
Floor Load
-
Noise Criteria
NC-40
Room Pressure
POSITIVE**
Floor finish
WSF
Note:
Dry Bulb Temp Cooling Range
78 F (25 C)
Lead Lining
-
Refer to PG-18-1 and PG-18-6
72 F (22 C)
Minimum Air Changes per Hour
-
Minimum % Outside Air
100
YES
ELECTRICAL
HOOD*
Steam
YES
Lighting
Power
Relative Humidity
50 %
Relative Humidity
30 %
General
100 FC, 2.5 W/SF General
180 WATTS
Special
-
Special
*
ALL
Emergency
Emergency
ALL
*SEE TYPE "B" CANOPY HOOD OVER VS-122;
SEE PG-18-6, CADD DETAIL NO. 11710-2.DWG
FOR STEAM AND HEAT GAIN CAPACITIES.
*(1) STERLIZER 600W CONTROL, (1) WARMER 1500W
**NEGATIVE PRESSURE IN EQUIPMENT ROOM.
PLUMBING AND MEDICAL GASES
YES
-
Cold Water
Medical Air
YES
-
Hot Water
Medical Vacuum
Sanitary Drain
YES
Oxygen
-
TELECOMMUNICATIONS
-
Acid Waste
Nitrous Oxide
-
Silver Recovery
-
-
Patient Monitor
Telephone
-
-
Anesthesia Evac
-
-
-
Nurse Call
Intercom
Code One
-
Public Addr.
-
-
CCTV
ADP
-
Radio
-
SPECIAL EQUIPMENT
None
Design Guide - Surgical Service
Design Standards
Sub-Sterile Room
Guide Plate:
5-6b
95 NSF (8.8 NSM)
Date: August 2005