ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
95 NSF (8.8 NSM)
Wall Finish
GYP. BOARD(SC)
AC Load Lights
4.0 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
1.9 W/SF+VS-123*
Base
AS REQUIRED
WSF
Ceiling Height
Number of People
1
Floor Load
-
6" (152 mm) INTEGRAL
Floor finish
Noise Criteria
NC-40
COVE BASE
Room Pressure
NEGATIVE
Note:
Lead Lining
-
Dry Bulb Temp Cooling Range
78 F (25 C)
Refer to PG-18-1 and PG-18-6
72 F (22 C)
Minimum Air Changes per Hour
-
Minimum% Outside Air
100
%
YES
ELECTRICAL
VS-123 HOOD*
Steam
YES
Lighting
Power
Relative Humidity
50 %
Relative Humidity
30 %
General
150 FC, 4.5 W/SF
General
180 WATTS
Special
-
Special
*
Notes:
ALL
Emergency
Emergency
ALL
*INTEGRAL CANOPY HOOD; SEE PG-18-6 CADD
Note:
DETAIL NO. 11710-1.DWG. FOR STEAM HEAT GAIN.
*(1) STERLIZER 600W CONTROL, (1) WARMER 1500W
PLUMBING AND MEDICAL GASES
YES
-
Cold Water
Medical Air
YES
-
Hot Water
Medical Vacuum
Sanitary Drain
YES
Oxygen
-
-
Acid Waste
-
-
TELECOMMUNICATIONS
Nitrous Oxide
Silver Recovery
-
-
-
Patient Monitor
-
Telephone
-
Anesthesia Evac
-
-
-
Nurse Call
Intercom
Code One
-
Public Addr.
-
-
CCTV
ADP
-
Radio
-
SPECIAL EQUIPMENT
None
Design Guide - Surgical Service
Design Standards
Sub-Sterile Room
Guide Plate:
5-7b
(Cabinet Enclosed Equipment)
95 NSF (8.8 NSM)
Date: August 2005