ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
150 NSF (14.0 NSM)
Wall Finish
GYP. BOARD(SC)
AC Load Lights
2.2 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
1.2 W/SF
Base
-
WSF
Ceiling Height
Number of People
1
Floor Load
100 PSF
6" (152 mm) INTEGRAL
Floor finish
Noise Criteria
NC-40
COVE BASE
Room Pressure
Negative
Lead Lining
-
Note:
Dry Bulb Temp Cooling Range
78 F (25 C)
Refer to PG-18-1 and PG-18-6
72 F (22 C)
Minimum Air Changes per Hour
4
Minimum % Outside Air
100
YES
ELECTRICAL
-
Steam
-
Lighting
Power
Relative Humidity
50 %
Relative Humidity
30 %
General
50 FC, 2.0 W/SF
General
1200 WATTS
Special
-
Special
*
-
Emergency
Emergency
-
PLUMBING AND MEDICAL GASES
24" (610 mm) OC ABOVE COUNTER
YES
-
Cold Water
Medical Air
YES
-
Hot Water
Medical Vacuum
Sanitary Drain
YES
Oxygen
-
-
Acid Waste
Nitrous Oxide
-
Silver Recovery
-
-
Plaster Trap
YES
Anesthesia Evac
-
TELECOMMUNICATIONS
Patient Monitor
-
Telephone
YES
-
-
Nurse Call
Intercom
Code One
-
Public Addr.
-
-
CCTV
ADP
-
Radio
-
SPECIAL EQUIPMENT
None
Design Guide - Surgical Service
Design Standards
Plaster and Splint
Guide Plate:
5-4b
Storage Room
150 NSF (14.0 NSM)
Date: August 2005