ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
100 NSF (9.2 NSM)
Wall Finish
GYP. BOARD(SC)
AC Load Lights
4.5 W/SF
-
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
12.0 W/SF
Base
-
WSF
Ceiling Height
Number of People
1
Floor Load
100 PSF
6" (152 mm) INTEGRAL
Floor finish
Noise Criteria
NC-45
COVE BASE
Room Pressure
NEGATIVE
Lead Lining
-
Dry Bulb Temp Cooling Range
78 F (25 C)
Note:
72 F (22 C)
Refer to PG-18-1 and PG-18-6
Minimum Air Changes per Hour
12(SA)
Minimum % Outside Air
100
YES
-
ELECTRICAL
Steam
-
Relative Humidity
50 %
Lighting
Power
Relative Humidity
30 %
General
100 FC, 4.0 W/SF
General
1000 WATTS
Special
-
Special
*
Emergency
ALL
Emergency
1000 WATTS
PLUMBING AND MEDICAL GASES
*(1) STRIP MOLD WITH DUPLEX RECEPTACLES 24" OC ABOVE COUNTER
YES
-
Cold Water
Medical Air
YES
-
Hot Water
Medical Vacuum
Sanitary Drain
-
Oxygen
-
Acid Waste
YES*
Nitrous Oxide
TELECOMMUNICATIONS
-
Silver Recovery
-
-
Anesthesia Evac
-
Patient Monitor
Telephone
YES
-
-
PART OF TELEPHONE
Nurse Call
Intercom
Code One
-
Public Addr.
-
-
*CONNECT CRP WASTE AND VENT TO
CCTV
ADP
EMPTY CONDUIT
NORMAL STACKS
Radio
-
SPECIAL EQUIPMENT
None
Design Guide - Surgical Service
Design Standards
Frozen Section Laboratory
Guide Plate:
5-2b
100 NSF (9.2 NSM)
Date: August 2005