ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
280 NSF* (26.0 NSM)
Wall Finish
GYP. BOARD(SC)
AC Load Lights
1.8 W/SF
ACROVYN ON CBB
Ceiling
GYP. BOARD
Wainscot
AC Load Equipment
4.0 W/SF
Base
9'-0" (2.75 METERS)
WSF
Ceiling Height
Number of People
2
6" (152 mm) INTEGRAL
Floor finish
Noise Criteria
NC-40
Floor Load
100 PSF
Room Pressure
(0)
COVE BASE
Notes:
Lead Lining -
Dry Bulb Temp Cooling Range
78 F (25 C)
Refer to PG-18-1 and PG-18-6
72 F (22 C)
Minimum Air Changes per Hour
-
*ADD 70 NSF FOR EACH O.R. OVER 4 INCLUDING CYSTOSCOPY
Minimum % Outside Air
100
YES
ELECTRICAL
-
Steam
-
Lighting
Power
Relative Humidity
50 %
Relative Humidity
30 %
General
50 FC, 1.5 W/SF
General
800 WATTS
Special
-
Special
*
Emergency
(1) FIXTURE
Emergency
-
*(1) STRIP MOLD W/DUPLEX RECEPTACLES 24" OC ABOVE COUNTER
PLUMBING AND MEDICAL GASES
YES
YES
Cold Water
Medical Air
YES
YES
Hot Water
Medical Vacuum
Sanitary Drain
YES
Oxygen
YES
TELECOMMUNICATIONS
Acid Waste
-
Nitrous Oxide
-
Silver Recovery
-
-
-
YES
Patient Monitor
Telephone
Anesthesia Evac
-
YES
-
Nurse Call
Intercom
YES
Code One
BEEPER*
Public Address
-
CCTV
ADP
EMPTY CONDUIT
-
Radio
SPECIAL EQUIPMENT
*AUDIO EMERGENCY ALARM FROM RECOVERY BEDS
None
Design Guide - Surgical Service
Design Standards
Anesthesia Workroom and
Guide Plate:
5-1c
Equipment Storage
280 NSF (26.0 NSM)
Date: August 2005