September 30, 1994
Design Standards
Dispatcher's Control Station
ARCHITECTURAL
Ceiling
AT
Wainscot
-
Ceiling Height
2700 (9'-0")
Base
RB
Wall Finish
PL (SC)
Floor Finish
VCT
Notes:
Slab Depression
-
0.1 X STERILE/NONSTERILE STORAGE
SPECIAL EQUIPMENT
ELECTRICAL
Lighting
Power
General
70 FC - 4 W/SF
General
Special
-
Emergency
-
Notes:
ADP
-
Telephone
-
Radio
-
Intercom
EMPTY CONDUIT
Notes:
Public Address YES*
*CONNECT TO HOSPITAL SYSTEM
HEATING, VENTILATING AND AIR CONDITIONING
Dry Bulb Temp Cooling F
76
Relative Humidity/Cooling 50%
Minimum % Outside Air
100
Minimum Air Changes/Hr
10
YES
Room Pressure
(0)
Noise Criteria
NC-40
AC Load - Equipment
2.2296 W/SM
Steam
-
Number of People
2
Notes:
-
PLUMBING AND MEDICAL GASES
Cold Water
-
Sanitary Drain
-
Hot Water
-
Reagent Grade Water
-
Laboratory Air
-
Medical Air
-
Laboratory Vacuum
-
Medical Vacuum
-
Other
-
Oxygen
-
Notes:
VA Design Guide -- Supply, Processing, & Distribution