Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
SCI Chief's Office 48
Function:
This space is intended to provide administrative facilities for the Chief of the SCI Center. It is to be
located in the Administrative Wing of the Center and must be accessible to SCI patients. Direct access to
secretarial space is also required.
Space Requirement:
200 NSF
Architectural:
Finish Code:
6-B
Floor Finish:
Carpet
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
40
Slab Depression:
None
Special Construction:
-
Hardware:
23
Doors:
3'-6" x 7'-0" wood or metal
Windows:
Desirable, see H-08-3, CS-31-1 & CD-35.
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
480w
Equipment: 450w
People:
300w, sensible
300w, latent
Electrical:
Lighting Levels:
Three Level Illum:
High: 70fc
Med
40fc
Low
20fc
Emergency Power:
-
Office of Facilities Management