Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Pool: Suits/Towels 47
Function:
This space is intended to provide for the storage and dispensing of clean swimwear and the collection
and cleaning of used swimwear. It is to be located at the entrance to the Therapeutic Pool.
Space Requirement:
210 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl*
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction: -
Hardware:
23 (45@vestibule entry)
Doors:
3'-6' x 7'-0" wood or metal
Windows:
None
*Ceramic Tile in Vestibule
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour:
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
-
Noise Criteria:
50
A/C Loads:
Lights:
-
Equipment:
-
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
-
Office of Facilities Management