Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Pool Dressing/Female - Shower/Toilet 46
Function:
This space is intended to provide changing and bathing facilities for the female patient population. While
intended primarily for the SCI patients there will likely be other patient users. To be located adjacent to
the Therapeutic Pool.
Space Requirement:
185 NSF
Architectural:
Finish Code:
2-G
Floor Finish:
Ceramic Tile (slip-resistant)
Base:
Ceramic Tile
Wall Finish:
Gypsum Wallboard/Paint*
Ceiling:
Acoustical Tile (SP)**
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction: -
Hardware:
-
Doors:
None Required
Windows:
None
*Full Ceramic Tile in Shower
**Plaster in Shower/Paint
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour:
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
-
Noise Criteria:
50
A/C Loads:
Lights:
-
Equipment:
-
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
One Ceiling Light
Nurse Call
Office of Facilities Management
235