Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Activities of Daily Living/Kitchen 43-A
Function:
This space provides a modified kitchen environment in which SCI patients are trained and evaluated as to
their ability to function independently.
Space Requirement:
See ADL/Living: The entire ADL Clinic is 450 NSF.
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
N/A
Doors:
None Required
Windows:
None Required
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
75w
Equipment: 450w
People:
100w, sensible
130w, latent
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power:
-
Office of Facilities Management
221