Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Occupational Therapy Treatment Clinic 42
Function:
This space is intended to accommodate physical, psychosocial and vocational evaluation and therapy.
Space Requirement:
0-30 SCI Beds: 720 NSF
31-60 SCI Beds: 780 NSF
61-100 Beds: 1080 NSF
Over 100 SCI Beds: 1344 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
82
Doors:
2@ 3'-0" x 7'-0" wood or metal, upper half=laminated safety glass.
Windows:
Desirable, see PG-18-3, Topic 1, Codes and Standards.
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
1350w
Equipment: 1050w
People:
1440w, sensible
3000w, latent
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
One Ceiling Light
Nurse Call
Office of Facilities Management
217