Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Activities of Daily Living/Bathroom 43-C
Function:
This space provides a similar bathroom environment to that found in the community. Here the patient's
ability to function independently will be evaluated.
Space Requirement:
See ADL/Living. The entire ADL Clinic is 450 NSF.
Architectural:
Finish Code:
2-G
Floor Finish:
Ceramic Tile (slip-resistant)
Base:
Ceramic Tile
Wall Finish:
GWB/Ceramic Wainscot 4'-0"
Ceiling:
Acoustical Tile*
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction: -
Hardware:
14
Doors:
2'-8" x 7'-0" wood
Windows:
Not Required
*Plaster/Paint in shower
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
35
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power:
-
Office of Facilities Management
225