Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Hydrotherapy 37
Function:
This space is intended to provide hydrotherapy facilities for SCI Inpatients. Treatments include both
muscular and skin reconditioning therapies. This space should be located adjacent to and accessed
through the Physical Therapy Clinic.
Space Requirement:
384 NSF
Architectural:
Finish Code:
2-C
Floor Finish:
Ceramic Tile (slip-resistant)
Base:
Ceramic Tile
Wall Finish:
Ceramic Tile
Ceiling:
Plaster/Paint
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
4" ceramic tile sloped to drain. See PG-18-3, Topic 6, Floor Slab Depressions.
Special Construction:
-
Hardware:
69
Doors:
4'-0" x 7'-0" wood or metal
Windows:
None Required
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour: 6 (100% Exhaust)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)
Noise Criteria:
45
A/C Loads:
Lights:
300w
Equipment: 600w, sensible, 1200w
People:
500w, sensible
650w, latent
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power:
One Ceiling Light
Nurse Call
Office of Facilities Management
200