Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Outpatient/G.U. Clinic Clean Utility 33
Function:
This space will provide primary storage for both the Outpatient and G.U. Clinics. In addition to stocks of
medical supplies this space will also contain the supply carts used by the G.U. technicians to perform
intermittent catheterization.
Space Requirement:
150 NSF
Architectural:
Finish Code:
1-P
Floor Finish:
Base:
Vinyl
Wall Finish:
Veneer Plaster*
Ceiling:
Gypsum Wallboard/Paint
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction: One Hour Fire-Rated enclosure plus sprinklers.
Hardware:
43
Doors:
3'-8" x 7'-0" wood or metal, optional wireglass view panel, "C" Label.
Windows:
None
*Special Coating, see Mspec #09815
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
Positive
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
225w
Equipment: 300w
People:
150w, sensible
150w, latent
Electrical:
Lighting Levels:
Gen. Illum: 10fc
Emergency Power:
Nurse Call