Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Outpatient/G.U. Clinic Nurse Station 32
Function:
This space serves as the control point for the Outpatient/G.U. Clinics. The space provided
accommodates an outpatient clerk and a nursing assistant. Outpatient records are also stored here.
Direct visual control of the front door and waiting area is required.
Space Requirement:
150 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Veneer Plaster/Vinyl Fabrication
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
N/A
Slab Depression:
None
Special Construction:
-
Hardware:
-
Doors:
None
Windows:
None
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
850w
Equipment: 450w
People:
300w, sensible
300w, latent
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Task Illum: 70fc
Emergency Power:
One Receptacle
Nurse Call
Medical Gas Alarms
Office of Facilities Management