Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Patient Clothing & Luggage Storage 22-A
Function:
This space is to accommodate SCI patient's seasonal clothing and luggage storage. This space is to be
wheelchair accessible.
Space Requirement:
6 NSF/Bed, Long Term Beds only.
Architectural:
Finish Code:
4D
Floor Finish:
Concrete
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Exposed
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
13
Doors:
4'-0" x 7'-0" wood or metal
Windows:
None
HVAC:
Temperature:
Summer: -
Winter:
72
Min. Air Changes/Hour:
4
Min. % Outside Air:
-
Pressure:
(0)
% Filtration:
-
Noise Criteria:
A/C Loads:
Lights:
225w
Equipment: 150w
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power:
-
Office of Facilities Management