Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Building Management Storage 22
Function:
This space is intended for the storage of bulk maintenance supplies and large equipment used for
environmental sanitation.
Space Requirement:
100 NSF/Floor
Architectural:
Finish Code:
8-F
Floor Finish:
Latex Mastic or Resil. Sheet**
Base:
Latex Mastic or Resil. Sheet**
Wall Finish:
Veneer Plaster*
Ceiling:
Acoustical Tile/Special-Faced
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction: -
Hardware:
13
Doors:
3'-8" x 7'-0" wood or metal, louver as required.
Windows:
None
*Special Coating, see Mspec #09815
**Heat Welded Seams, see Mspec #09666
HVAC:
Temperature:
Summer: -
Winter:
72
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
40
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power:
-
Office of Facilities Management
132