Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Dining Room 18
Function:
This space is intended to accommodate a 30 Bed Unit with each meal served in one shift, or two 30 Bed
Units with each meal served in two shifts. Peak usage is during the afternoon and evening meals. It is
desirable to have this space adjacent and openable to the Multi-purpose Recreation Space to
accommodate unusually large gatherings.
Space Requirement:
1,600 NSF
Architectural:
Finish Code:
1-G
Floor Finish:
Base:
Vinyl
Wall Finish:
GWB/Vinyl Fabric Wallcover
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
35
Slab Depression:
None
Special Construction:
-
Hardware:
82
Doors:
2@3'-0" x 7'-0" wood or metal, upper half=laminated safety glass.
Windows:
Very desirable, see PG-18-3, Topic 1, Codes and Standards.
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
1560w
Equipment: 750w
People:
3750w, sensible
4750w, latent
Electrical:
Lighting Levels:
High: 30fc
Med: 20fc
Low: 10fc
Emergency Power:
Two Ceiling Lights
Night Lights
Office of Facilities Management