Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Visitor's Toilets 17-A
Function:
These facilities are to be contiguous to the Visitor's Lounge but accessed from the corridor in front of the
Lounge.
Space Requirement:
Male: 52 NSF
Female: 52 NSF
Architectural:
Finish Code:
2-G
Floor Finish:
Ceramic Tile (slip-resistant)
Base:
Ceramic Tile
Wall Finish:
GWB/4'-0" Ceramic Wainscot
Ceiling:
Acoustical Tile/Special-Faced
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
18
Doors:
3'-0" x 7'-0" wood or metal, louver as required.
Windows:
None
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
40
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
-
Office of Facilities Management
111