Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Transfer Equipment Storage 11-A
Function:
This space is intended for the storage of standard and electric wheelchairs, litters, lifts and mobilizer or
any other device required to move patients in and out of bed.
Space Requirement:
7 NSF/Bed
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
13
Doors:
4'-0" x 7'-0" wood or metal, optional glass view panel.
Windows:
None Required
HVAC:
Temperature:
Summer: -
Winter:
72
Min. Air Changes/Hour:
6
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
40
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power: -
Office of Facilities Management