Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Litter Storage 11
Function:
This space is intended for the storage of litters and other large pieces of equipment. It should be located
in opposition to the Transfer Equipment Storage Area (Guideplate 11-A) so that storage opportunities are
dispersed.
Space Requirement:
10 NSF/Bed
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
13
Doors:
4'-0" x 7'-0" wood or metal, optional glass view panel.
Windows:
None Required
HVAC:
Temperature:
Summer: -
Winter:
72
Min. Air Changes/Hour:
6
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
40
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power: -
Office of Facilities Management
84