Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Medical Equipment Storage 11-B
Function:
This space is intended for the storage of equipment too delicate to be stored in either the Litter or
Wheelchair/Transfer Equipment Storage Rooms, and too large to be stored in the Clean Utility Room.
Space Requirement:
3 NSF/Bed
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
-
Hardware:
13
Doors:
4'-0" x 7'-0" wood or metal, optional glass view panel.
Windows:
None Required
HVAC:
Temperature:
Summer: -
Winter:
72
Min. Air Changes/Hour:
6
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
-
Noise Criteria:
40
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power: -
Office of Facilities Management