Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Soiled Linen 8-A
Function:
This space is intended to provide a temporary holding area for soiled linen on its way to the Laundry.
Space Requirement:
60 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
1 Hour Fire-rated Enclosure and Sprinklers.
Hardware:
43
Doors:
3'-10" x 7'-0" wood or metal, "C" Label, optional wire-glass view panel.
Windows:
None
HVAC:
Temperature:
Summer: -
Winter:
72
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
30% (PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
-
Equipment: -
-
People:
Electrical:
Lighting Levels:
Gen. Illum: 20fc
Emergency Power: -
Office of Facilities Management
77