Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Clean Linen 8
Function:
This space is intended for the storage of clean linen on carts and/or fixed shelves. It should be centrally
located and is for staff access only.
Space Requirement:
80 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
1 Hour Fire-Rated Enclosure and Sprinklers.
Hardware:
43
Doors:
3'-10" x 7'-0" wood or metal "C" Label, optional wire-glass view panel.
Windows:
None
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
72@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
Positive
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
120w
Equipment: 150w
People:
90w, sensible
95w, latent
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power: -
Office of Facilities Management
74