Design Standards
Treatment Planning Computer Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2745 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
Resilient Base
Noise Criteria:
NC-40
Floor Finish:
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes: 1. 3'-0" Wide door with tempered
Relative Humidity/Heating:
30%
glass view window
Minimum Air Changes/Hr.:
4
Room Pressure:
0
SPECIAL EQUIPMENT
AC Load-Equipment:
140w/sm (13w/sf)
AC Load Lighting:
26w/sm (2.4w/sf)
None
Number of People:
4
LIGHTING
--
Notes:
General:
50fc - 1.3 w/sf
--
Special:
--
Notes:
1. 600mm x 1200mm (2' x 4')
PLUMBING AND MEDICAL GASES
fixture, acrylic prismatic lens,
Cold Water:
--
W/3-F32T8 lamps, 4100 deg. K,
Hot Water:
--
CRI=75 (minimum).
Laboratory Air:
--
Laboratory Vacuum:
--
POWER
Sanitary Drain:
--
Reagent Grade Water:
--
General:
Medical Air:
--
Emergency:
--
Medical Vacuum:
--
Notes:
--
Oxygen:
--
COMMUNICATION
Notes:
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
GUIDE PLATE 5-2