FINAL DRAFT 2-29-96
Revised 10/96
Design Standards
Mold Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2745 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
GWB
Minimum % Outside Air:
15%
Wainscot:
--
Yes
Base:
Resilient Base
Noise Criteria:
NC-40
Floor Finish:
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
10
SPECIAL EQUIPMENT
Room Pressure:
Negative
AC Load-Equipment:
162w/sm (15w/sf)
None
AC Load Lighting:
2.6 w/sm (2.4 w/sf)
LIGHTING
Number of People:
4
Special Exhaust:
Yes
General:
50fc - 2.4w/sf
Special:
--
Notes:
--
Notes:
1. 600mm x 1200mm (2' x 4')
PLUMBING AND MEDICAL GASES
fixture, acrylic prismatic lens,
Cold Water:
--
W/2-F32T8 lamps, 4100 deg. K,
Hot Water:
--
CRI=85 (minimum).
Laboratory Air:
--
Laboratory Vacuum:
--
POWER
Sanitary Drain:
--
General:
Reagent Grade Water:
--
Emergency:
--
Medical Air:
--
Notes:
Medical Vacuum:
--
Oxygen:
--
power tools.
Notes:
1. Shop compressed air might be
.
required.
2. Plaster trap might be required.
COMMUNICATION
ADP:
--
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
1. Conduit and junction boxes
required for electronic
access security system.
VA DESIGN GUIDE
GUIDE PLATE 5-1