Final Draft 12-31-95
Revised May 1997
Design Standards
Radiology Film Records Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
Resilient base
100%
Floor Finish:
Noise Criteria:
NC-40
in Viewing Area
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes: 1. 1060 mm (3'-6") wide doors in film
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
4
library.
Room Pressure:
0
2. 1 hour fire resistant rated
AC Load-Equipment:
construction around film library.
Common & Mulit Viewing: 43 W/sm(4W/sf)
Coordinate floor loading
Film Lab: 16W/sm (1.5W/sf)
requirements in film library with
AC Load Lighting:
Structural Engineer.
Common & Mulit Viewing: 11 W /sm(.1 W/sf)
Film Lab: 15 W/m 2 (1.4 W/sf)
SPECIAL EQUIPMENT
Number of People:
Film Library: 3
None
Multi-Viewing: 4
Common Viewing: 6
LIGHTING
--
Notes:
--
General:
Common Viewing: 30 FC
Multi Viewing: 30FC
PLUMBING AND MEDICAL GASES
Film Library: 50FC
Special:
--
Cold Water:
--
Notes: 1. 600 mm x 1200 mm (2' x 4')
Hot Water:
--
Laboratory Air:
--
acrylic prismatic lens, W/2-F32T8
Laboratory Vacuum:
--
lamps, 3500 deg. K, CRI=75
Sanitary Drain:
--
(minimum).
Reagent Grade Water:
--
Medical Air:
--
POWER
Medical Vacuum:
--
Oxygen:
--
General:
Notes:
--
Emergency:
--
Notes:
--
COMMUNICATION
ADP:
--
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN GUIDE
RADIOLOGY SERVICE
PAGE 5-2