Final Draft 12-31-95
Revised May 1997
Design Standards
Special Procedures (non-affiliated Control Room)
COMMUNICATION
PLUMBING AND MEDICAL GASES
ADP:
--
Cold Water:
Yes
Radio:
--
Hot Water:
Yes
Telephone:
Yes
Laboratory Air:
--
Intercom:
Yes
Laboratory Vacuum:
--
Pub. Addr:
--
Sanitary Drain:
Yes
Reagent Grade Water:
--
Notes: 1. Nurse Call in toilet room to
Medical Air:
Yes
annunciate at reception desk.
Medical Vacuum:
Yes
Oxygen:
Yes
Notes:
--
CONDITIONING
Dry Bulb Temp Cooling:
25C (78F)
22C (72F)
Minimum % Outside Air:
15%
Yes
Noise Criteria:
--
Steam:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
Special Procedures: 8
Control Room: 4
Room Pressure:
Special Procedures: Negative
All Others: 0
AC Load Lighting:
for
Special Procedures: 39 W/sm (3.6 W/sf)
Control Room: 26 W/sm (2.4 W/sf)
AC Load-Equipment:
Special Procedures: 65 W/sm (6W/sf)
Control Room: 13,000 Btu/hr - 3752W)
Number of People:
6 for Procedure;
All Others: 3
--
Notes: 1. Provide a dedicated AC unit for
computer room sized to handle a
minimum of 3 tons of cooling. Verify
cooling capacity and other specific
requirements with the equipment
manufacturer on a specific project.
VA DESIGN GUIDE
RADIOLOGY SERVICE
PAGE 4-4