Final Draft 12-31-95
Revised May 1997
Design Standards
Radiographic Fluoroscopic Room w/Control
CONDITIONING
Dry Bulb Temp Cooling:
24C (75F)
22C (72F)
Minimum % Outside Air:
15%
Yes
Noise Criteria:
NC-40
Steam:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.: radiographic supply: 6
Room Pressure:
negative for radiographic:
Toilet: negative
AC Load Lighting:
35 W/m 2 (3.2 W/sf)
AC Load-Equipment:
Radiographic: 97 W/sm (9 W/sf
Number of People:
6
Special Exhaust:
--
Notes: 1. See HVAC Design Manual for
Hospital Projects for lead wrapping of
ductwork penetrating lead lined walls.
PLUMBING AND MEDICAL GASES
Cold Water:
Yes
Hot Water:
Yes
Laboratory Air:
--
Laboratory Vacuum:
--
Sanitary Drain:
Yes
Reagent Grade Water:
--
Medical Air:
Yes
Medical Vacuum:
Yes
Oxygen:
Yes
Notes:
--
VA DESIGN GUIDE
RADIOLOGY SERVICE
PAGE 4-3