Final Draft 12-31-95
Revised May 1997
Design Standards
Dedicated Chest Room
CONDITIONING
Dry Bulb Temp Cooling:
24C (76F)
25C (78F)
Minimum % Outside Air:
15
--
Noise Criteria:
NC-35
Steam:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
4
Room Pressure:
0
AC Load Lighting:
43 W/m ( 4 W/sf)
AC Load-Equipment:
65 W/m (6 W/sf)
Number of People:
6
--
Notes: 1. See HVAC Design Manual for
Hospital Projects for lead wrapping of
ductwork penetrating lead lined walls.
PLUMBING AND MEDICAL GASES
Cold Water:
Yes
Hot Water:
Yes
Laboratory Air:
--
Laboratory Vacuum:
--
Sanitary Drain:
Yes
Reagent Grade Water:
--
Medical Air:
Yes
Medical Vacuum:
Yes
Oxygen:
Yes
Notes:
--
VA DESIGN GUIDE
RADIOLOGY SERVICE
PAGE 4-2