FINAL DRAFT 9/6/95
UPDATED NOV. 1996
Design Standards
Computer Image and Data Processing Area
ARCHITECTURAL
CONDITIONING
Ceiling:
Acoustical ceiling tile
0
0
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling :
25 C (78 F)
0
0
Wall Finish:
Paint
22 C (72 F)
Wainscot:
---
Minimum % Outside Air:
15%
Base:
Resilient Base
---
Floor Finish:
Noise Criteria:
NC-40
Slab Depr.:
---
Steam:
---
Notes:
1050 mm (3'-6") wide door with
Relative Humidity/Cooling:
50%
tempered-glass view window
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
2
SPECIAL EQUIPMENT
Room Pressure:
0
2
AC Load-Equipment:
160 w/m (15 w/sf)
---
2
AC Load-Lighting:
20 w/m (1.8 w/sf)
ELECTRICAL LIGHTING
Number of People:
6
---
General:
30FC
Notes:
1. Verify equipment AC load as
Notes:
1. 600 mm x 1200 mm (2' x 4')
per actual equipment used.
fluorescent
light
fixture, 18 parabolic louver,
PLUMBING AND MEDICAL GAS
W/3-F32T8 lamps, 4100 deg. K,
CRI=85 (minimum).
Cold Water:
---
Hot Water:
---
POWER
Laboratory Air:
---
Laboratory Vacuum:
---
General:
Sanitary Drain:
---
Emergency:
---
Reagent Grade Water:
---
Notes:
---
Medical Air:
---
Medical Vacuum:
---
ADP:
Yes
Oxygen:
--
Radio:
---
Notes:
---
Telephone:
Yes
Intercom:
---
Public Addr:
---
Notes:
---
VA DESIGN GUIDE
NUCLEAR MEDICINE SERVICE
5-1