FINAL DRAFT 9/6/95
UPDATED NOV. 1996
Design Standards
Thyroid Uptake
ARCHITECTURAL
CONDITIONING
Ceiling:
Acoustical ceiling tile
o
0
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling :
25 C (78 F)
0
0
Wall Finish:
Paint
22 C (72 F)
Wainscot:
---
Minimum % Outside Air:
Base: Integral welded seam sheet flooring base
15%
Floor Finish:
Welded seam sheet flooring
--
Slab Depr.:
---
Noise Criteria:
NC-40
Notes:
1200 mm (4'-0") wide door
Steam:
---
Relative Humidity/Cooling:
50%
SPECIAL EQUIPMENT
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
2
none
Room Pressure:
0
2
ELECTRICAL LIGHTING
AC Load-Equipment:
54 w/m (5 w/sf)
2
General:
30FC
AC Load-Lighting:
15 w/m (1.4 w/sf)
Notes:
1600 mm x 1200 mm (2' x 4')
Number of People:
3
fluorescent
light
---
fixture, acrylic prismatic lens,
Notes:
W/3-F32T8 lamps, 4100 deg. K,
PLUMBING AND MEDICAL GAS
CRI=85 (minimum).
Cold Water:
Yes
POWER
Hot Water:
Yes
Laboratory Air:
--
General:
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
Yes
Notes:
1. Special receptacle for thyroid
Reagent Grade Water:
--
uptake unit ( coordinate with
Medical Air:
--
supplier)
Medical Vacuum:
--
--
Oxygen:
ADP:
Yes
Notes:
Radio:
---
Telephone:
Yes
Intercom:
Yes
Public Addr:
---
Notes:
---
VA DESIGN GUIDE
NUCLEAR MEDICINE SERVICE
4-4