June 99
B. NUSIG manuals of design are pre-calculated from
0.05g through 1.00g in increments of 0.15g.
4.4 CALCULATIONS: Unless otherwise shown by
SMACNA or NUSUG, provide detailed structural
calculations for VA's review on the design hangers,
supports, anchor bolts and connections. Show sizes,
spacing, and length for securing to structural
members, and length and sizes of welds anchored to
steel members.
4.5 DRAWINGS:
A. Where SMACNA or NUSIG details are incomplete
or not applicable, show complete seismic restraint
requirements and coordinate with the specifications.
Coordinate mechanical work with architectural and
structural work. Special provisions and details may be
required.
B. Ductwork and Piping Plans and Sections: Show
the locations of required restraints with reference to
SMACNA, NUSIG, or special restraint, whichever is
applicable.
C. Equipment restraints: Show special details where
required. Pay attention to suspended equipment.
5.
DOCUMENTATION AND MISCELLANEOUS
REQUIREMENTS:
5.1
GENERAL: Refer to Article 6, APPLICABLE
PUBLICATIONS for the applicable requirements. Refer to
the VA Standard Details for the symbols and abbreviations
which shall be used on all drawings and specifications. To
avoid any confusion and dispute, nomenclature on the
drawings shall correspond exactly to nomenclature in the
VA Master Specifications.
5.2
EQUIPMENT SCHEDULES:
A.
List equipment Schedules in the following order,
vertically, from left to right, to facilitate checking and
future reference. Do not show trade names or
manufacturers model numbers.
1.
Air Conditioning Design Data (outdoor design and
indoor design conditions for the various
occupancies)
VA Design Guide -- National Cemetery Administration
Page 5 -64