June 99
B.
Install data service cabling in the same conduit with
telephone wiring to each workstation within the
building. The incoming data lines and lines between
buildings shall be installed in separate conduits.
C. Provide incoming data cabling as required to
accommodate two lines per workstation (one 56K
digital circuit) from the local company point of
connection to the main telephone closet of the
Administration/ Maintenance Complex. Refer to Article
2.12 for incoming conduit requirements.
1.
Provide the following cables between the
Administration/Maintenance Complex (main
telephone closet) and Remote Buildings (two lines
per workstation):
a.
Distances less than 100 m (300 linear feet):
10 Baset, UTP level 5, 24 AWG plenum 4
pair cable.
b.
Distances less than 2 km (1.24 miles)
multimode fiber cable, 2 strand, 62.5 x 1.25
microns.
2.
Provide one Category 5 cable - 10 Baset, UTP
Level 5, 24 AWG plenum 4 pair cable, labeled
"P1, P2, P3..." between computer printer and
each workstation (maximum 7 workstation
connections to a printer). Provide 19 mm
(3/4") conduit, with outlet box as appropriate
for the number of workstations connected to
each printer, between each workstation and
printer.
12.
SECURITY SYSTEMS:
12.1
Requirements;
A.
Provide a motion detection system for the following:
1.
Entrances to all buildings
2.
Information Center Lobby
3.
Maintenance Yards (Personnel entrances)
4.
Administrative Offices
VA Design Guide -- National Cemetery Administration
Page 5 -42