June 99
A.
Investigate and provide a fire alarm system to meet the
requirements of NFPA.
B.
Fire alarm system may be a manual non-coded,
audible/visual type system with a tie-in to the local
municipal fire alarm system.
10.
TELEPHONE SYSTEMS:
10.1
Requirements:
A.
Investigate and provide facilities (underground
conduits) as required for the installation of the
telephone service. See Article 2.
B.
Provide a minimum 19 mm (3/4") conduit and outlet
box with a triple phone jack (one RJ 11 and two RJ 45)
at each workstation in each building where required.
Install junction box above ceiling for drops to printers.
Provide conduit and outlet box with one phone jack (RJ
11) in the main telephone closet.
C. Provide incoming telephone cabling as required to
accommodate one line per workstation, fax lines, and
spares from local telephone company point of
connection to the main telephone closet of the
Administration/Maintenance Complex. Refer to Article
2.12 for incoming conduit requirements.
1. Provide one Category 3 telephone cable - 19
gauge/standard color code cable between the
Administration/Maintenance Complex (main telephone
closet) and Remote Buildings to accommodate one
line per workstation plus spares.
2, Provide one Category 3 telephone cable - 19
gauge/standard color code/ 2 pair, labeled "T" between
telephone closet and each workstation.
11.
AUTOMATIC DATA PROCESSING (ADP) SYSTEMS:
11.1
Requirements:
A.
Investigate and provide facilities (underground conduits
as required for the installation of the ADP service. See
Article 2.
VA Design Guide -- National Cemetery Administration
Page 5 -41