*Additional 8" of accessible space must be available above the ceiling to accommodate
ceiling-mounted operating microscopes: Otherwise, ceiling height must be 10'-2".
**Life Safety Code, NFPA-101, requires a means of egress to have a minimum headroom of 7'-6" and
any projection from the ceiling to be at least 6'-8" from the floor.
***Some manufacturers' equipment for cardiac cath and special procedures rooms may require more
than 9'-6". Verify specific requirements with VA before establishing a firm ceiling height in these
spaces.