JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
Areas
Summer DB
Summer
Winter
Winter
(F)
Relative
DB ( F)
Relative
Humidity
Humidity (%)
(%)
110
--
40
--
Examination Rooms
75
50
78
30
Laboratories
75
50
72
30
Locker Rooms
78
50
72
30
Lounges
78
50
72
30
Mechanical Equipment
Ventilation Only
50
--
Rooms (MERs)
Minor O.R.s (Trauma
75
50
78
30
Rooms)
Motor Vehicle
Ventilation Only
70
--
Maintenance/Storage
MRI Units
76
50
78
30
Offices, Conference
78
50
72
30
Rooms
Pharmacy
72
50
72
30
Recovery Units
75
50
75
30
Smoking Area
78
50
72
30
SPECIAL PROCEDURE
ROOMS*
Bronchoscopy
73
50
78
30
Cardiac Catheterization
62-80
45-55
62-80
45-55
Colonoscopy/EGD
73
50
78
30
Cystoscopy
73
50
78
50
Endoscopy
73
50
78
30
Fluoroscopy
73
50
78
30
GI (Gastrointestinal)
73
50
78
30
Proctoscopy
73
50
78
30
Sigmoidoscopy
73
50
78
30
Supply Processing
76
50
72
30
Distribution (SPD)
Ethylene Oxide (ETO)
Ventilation only
MERs
Telephone Equipment
65-75
40-60
65-75
40-60
Rooms
104
(Maximum)
Treatment Rooms
75
50
78
30
Warehouses
Ventilation
60
--
Only
Triage
75
50
78
3-
These are design conditions and not operating limits. All thermostats shall be adjustable between 60 to 85
degrees F.
The summer indoor design relative humidity shown in the Table above need not be maintained by any
humidity control either at the air terminal units or at the air-handling units. These values merely represent
the design reference points and, in actual practice, would vary due to the predetermined air quantities and
fluctuations in the internal heat loads. However, the winter indoor design relative humidity shall be
maintained by humidity control either at the air terminal units, or at the air handling unit or both.
Part I: Basic Solicitation Requirements Page 89 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages