6.2.5.2.1 Safety Glazing:
Glaze windows occurring in security exam rooms or security holding room with 7/16" thick laminated glass.
Provide laminated glass only for interior panes of double-glazed windows.
6.2.5.2.2 Screens:
Provide insect screens only on operable windows in spaces which are not air conditioned.
Provide bird screens on mechanical ventilation supply and exhaust openings in exterior walls. Provide
insect screens on the inside of louvered openings in exterior walls where there are no duct connections.
Provide security screens on windows where required by Physical Security requirements in Section 4 of this
solicitation.
Editing Note: Coordinate with Paragraph 6.2.3.
6.2.5.3 EXTERIOR DOORS:
Entrance doors shall be //revolving// //automatic sliding// //swinging// anodized aluminum construction with
safety glazing and shall comply with energy requirements as specified for exterior windows.
Swinging exterior doors and frames, except entrance doors, shall be heavy duty, insulated, full flush,
hollow steel construction. Exterior doors shall be weather-stripped, shall be self-closing, and shall open
outward. Door hardware shall comply with applicable portions of Section 7 of this solicitation. Provide
latch guards and hinges with non-removable pins to deter tampering or unauthorized entry.
Doors for vehicular access, including doors to //warehouse,// //engineering shops,// //spaces containing
building service equipment,// //and enclosed ambulance entry// shall be //insulated, industrial grade
sectional overhead doors// //overhead coiling doors//. Nominal size of the door opening shall be //8'-0"
wide by 9'-6" high// //[____]//. Doors shall be fully weather-stripped and include an electric operator and
manual chain hoist operation. Operator controls shall be located on the secure (interior) side of the
opening and shall incorporate a cylinder lock. Provide safeties, including door edge sensors. Overhead
door(s) shall not have vision lights.
6.2.5.3.1 Automatic Doors:
Design automatic doors to operate manually in event of power failure. Equip controls with safety devices
for pedestrian protection. Provide door operator controls and equipment that are easily accessible for
maintenance. Design automatic doors to open from both sides.
Automatic doors are required at the following locations:
Sliding doors operated by motion detectors and an electric-eye safety device with emergency
breakaway features at Patient entrances. (Use swinging doors with mat operation in lieu of sliding
doors where dictated by conditions.)
Swinging doors, mat operation (requires floor-slab depression): Ambulance entrance
Swinging doors, pull-chain operation: Doors between loading platform and corridors.
6.2.5.4 ROOFS:
6.2.5.4.1 Parapet Walls, Roof Structure, And Walkways:
Masonry parapet walls are potential sources of water penetration, unequal thermal expansion, additional
structural loads, and increased costs. Therefore, do not use such walls for any building unless specifically
permitted by the Contracting officer. Proposed parapet walls must be justified by aesthetic, functional or