JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
over the platform with 14-feet clearance from grade to the underside of the canopy. Provide a stair or a
ramp to the platform; for platforms which are more than 50-feet long, provide a stair or a ramp at each end.
6.2.4
CANOPIES:
Noncombustible canopies or covered walkways are required from the outpatient clinic building to locations
listed in Paragraph 5.4.3 of this solicitation.
Maintain soffits over passageways under portions of buildings, canopies, or overhanging wings that extend
over truck and public bus traffic areas, at a height that will provide 14-feet minimum head room. Maintain a
grade either side of the passageway to provide the required head room for the longest wheel base trailer
permitted by the State.
6.2.5
ENCLOSURE SYSTEMS:
6.2.5.1 WALLS:
Exterior wall systems shall be of durable and permanent materials as acceptable to the Contracting
Officer. Materials and colors shall be consistent with the overall design concept, structural requirements,
and provide the level of physical security required by this solicitation.
Walls shall be designed to prevent moisture penetration. Detail and construct moisture barriers, wall
cavities and weeps, or other features as necessary to prevent damage to wall components or entry of
moisture into building.
Design for heat loss or gain in accordance with energy criteria in this solicitation. Provide noncombustible
insulation in wall cavities. Provide vapor barrier at appropriate side of wall construction based on local
climatic conditions.
Structural design of walls shall comply with Paragraph 6.1. The weight of masonry walls or veneer shall
be supported by the structural frame at each floor.
Fire resistance shall be as required by applicable codes for construction type and exposure.
Editing Note: include following paragraph if sound
control is necessary.
Design walls for sound transmission control from external sources at sites near airports, freeways, //[___]//
or heavy city traffic.
6.2.5.2 WINDOWS AND SCREENS:
Lessor shall provide windows as shown on the conceptual floor plan. Design windows in accordance with
energy requirements in HVAC Section of this solicitation. Energy-conservation requirements will result in
double-glazed windows for most locations. For double-glazed windows, provide a continuous thermal
break between inner and outer sash; also between inner and outer frame components including window
sill. Where double-glazed windows are used, enclose horizontal venetian blinds between the two glazed
surfaces wherever the type of window will accommodate this feature.
Window sills/stools shall be a minimum of 18 inches above the finished floor.
Operable windows are more costly than fixed windows and more subject to drafts, leaks, and maintenance
problems. The Contracting Officer must approve use of operable windows.
Windows shall comply with Physical Security requirements in Section 4 of this solicitation.
Part I: Basic Solicitation Requirements Page 75 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages