JULY 2005
Design Standards
Gastric (Esophageal) Motility Procedure Room
ARCHITECTURAL
COMMUNICATION/SPECIAL SYSTEMS
Coordinate with SFO; refer to Template SFO
Coordinate with SFO; refer to Template SFO
Section 7, and Schedule C.
Sections 6.7.8, 6.7.9, and Schedule B.
Ceiling:
AT
Data:
Yes
Ceiling Height:
2740 mm (9'-0")
Telephone:
Yes
Wall Finish:
Painted GWB
Intercom:
--
Wainscot:
CT in Toilet Room
Nurse Call:
Yes
Base:
Resilient Sheet Flooring
Public Address:
--
CT in Toilet Room
Radio/Entertainment: --
Floor Finish:
Resilient Sheet Flooring
MATV:
--
CT in Toilet Room
CCTV:
--
Slab Depression:
--
MID:
--
Sound Protection:
--
Security/Duress:
--
Notes:
--
VTEL:
--
VA Satellite TV:
--
Notes:
--
LIGHTING
Coordinate with SFO; refer to Template SFO
Section 6.7, 6.7.1, 6.7.5.
CONDITIONING
General:
50-100 FC
Coordinate with SFO; refer to Template SFO
Special:
--
Section 6.5.
Notes:
22C (73F)
Dry Bulb Temp Cooling:
cent light fixture with
26C (78F)
acrylic prismatic lens.
Minimum % Outside Air:
2. 2' X 2' recessed
Yes
fluorescent light fixture
Noise Criteria:
NC-40
with acrylic prismatic
Steam:
--
lens.
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
POWER
Minimum Air Changes/Hr.:
10
Coordinate with SFO; refer to Template SFO
Room Pressure:
Negative
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
AC Load-Equipment:
6 W/SF
AC Load-Lighting:
1.6 W/SF
General:
Yes
Number of People:
3
Emergency:
--
--
Notes:
1. Junction box x-ray
Notes:
--
illuminator. Connect
per equipment
PLUMBING AND MEDICAL GASES
manufacturer.
Coordinate with SFO; refer to Template SFO
mounted junction box
Section 6.6 and Schedule B
for exam and treatment
Cold Water:
Yes
table. Connection to
Hot Water:
Yes
equipment per
Laboratory Air:
--
manufacturer. Provide
Laboratory Vacuum:
--
dedicated circuit. Verify
Sanitary Drain:
Yes
wattage, voltage, and
Reagent grade Water:
--
phase.
Medical Air:
--
3. Portable exam light.
Medical Vacuum:
--
Oxygen:
--
Notes:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
3-9.3