JULY 2005
Design Standards
Orthopedic Clinic / Cast Room
ARCHITECTURAL
CONDITIONING
Coordinate with SFO; refer to Template SFO
Coordinate with SFO; refer to Template SFO
Section 7, and Schedule C.
Section 6.5.
Ceiling:
AT
26C (78F)
Dry Bulb Temp Cooling:
Ceiling Height:
2740 mm (9'-0")
22C (72F)
Wall Finish:
Painted GWB
Minimum % Outside Air:
Wainscot:
--
--
Base:
Resilient Sheet Flooring
Noise Criteria:
NC-40
Floor Finish:
Resilient Sheet Flooring
Steam:
--
Slab Depression:
--
Relative Humidity/Cooling:
50%
Sound Protection:
STC 40
Relative Humidity/Heating:
30%
Notes:
--
Minimum Air Changes/Hr.:
10
LIGHTING
Room Pressure:
Negative
AC Load-Equipment:
5.0 W/SF
Coordinate with SFO; refer to Template SFO
AC Load-Lighting:
1.6 W/SF
Section 6.7, 6.7.1, 6.7.5.
Number of People:
4
General:
1. 70-100 FC for each
--
cubicle.
Notes:
--
2. 50 FC work area
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
cent light fixture with
Coordinate with SFO; refer to Template SFO
acrylic prismatic lens.
Section 6.6 and Schedule B
Cold Water:
Yes
POWER
Hot Water:
Yes
Coordinate with SFO; refer to Template SFO
Laboratory Air:
--
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
Laboratory Vacuum:
--
General:
Yes
Sanitary Drain:
Yes
Emergency:
--
Reagent grade Water:
--
Notes:
1. Junction box x-ray illumi-
Medical Air:
--
nator. Connect per
Medical Vacuum:
--
equipment manufacturer.
Oxygen:
--
2. Portable exam light.
Notes:
--
COMMUNICATION/SPECIAL SYSTEMS
Coordinate with SFO; refer to Template SFO
Sections 6.7.8, 6.7.9, and Schedule B.
Data:
Yes
Telephone:
Yes
Intercom:
--
Nurse Call:
--
Public Address:
--
Radio/Entertainment: --
MATV:
--
CCTV:
--
MID:
--
Security/Duress:
--
VTEL:
--
VA Satellite TV:
--
Notes:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
3-10.3