JULY 2005
Design Standards
ENT Examination Room
MATV:
--
ARCHITECTURAL
CCTV:
--
Coordinate with SFO; refer to Template SFO
MID:
--
Section 7, and Schedule C.
Security/Duress:
--
Ceiling:
GWB Lay-in Panels
VTEL:
--
Ceiling Height:
2740 mm (9'-0")
VA Satellite TV:
--
Wall Finish:
Painted GWB
Notes:
--
Wainscot:
--
Base:
Resilient Base
Floor Finish:
Slab Depression:
--
CONDITIONING
Sound Protection:
STC 40
Coordinate with SFO; refer to Template SFO
Notes:
--
Section 6.5.
23C (75F)
Dry Bulb Temp Cooling:
LIGHTING
26C (78F)
Coordinate with SFO; refer to Template SFO
Minimum % Outside Air:
15%
Section 6.7, 6.7.1, 6.7.5.
--
Noise Criteria:
NC-35
General:
50-100 FC
Steam:
--
Special:
--
Relative Humidity/Cooling:
50%
Notes:
Relative Humidity/Heating:
30%
cent light fixture with
Minimum Air Changes/Hr.:
6
acrylic prismatic lens.
Room Pressure:
0
AC Load-Equipment:
6 W/SF
POWER
AC Load-Lighting:
2 W/SF
Coordinate with SFO; refer to Template SFO
Number of People:
3
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
--
Notes:
--
General:
Yes
Emergency:
--
PLUMBING AND MEDICAL GASES
Notes:
mounted junction box
Coordinate with SFO; refer to Template SFO
for ENT chair. Connec-
Section 6.6 and Schedule B
tion to equipment per
Cold Water:
Yes
manufacturer. Provide
Hot Water:
Yes
dedicated circuit. Verify
Laboratory Air:
--
wattage, voltage, and
Laboratory Vacuum:
--
phase.
Sanitary Drain:
Yes
2. Junction box x-ray
Reagent grade Water:
--
illuminator. Connect
Medical Air:
--
per equipment
Medical Vacuum:
--
manufacturer.
Oxygen:
--
Notes:
--
COMMUNICATION/SPECIAL SYSTEMS
Coordinate with SFO; refer to Template SFO
Sections 6.7.8, 6.7.9, and Schedule B.
Data:
Yes
Telephone:
Yes
Intercom:
--
Nurse Call:
--
Public Address:
--
Radio/Entertainment: --
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
3-7.3