JULY 2005
Design Standards
Chemotherapy Treatment Room
Radio/Entertainment:
--
ARCHITECTURAL
MATV:
--
Coordinate with SFO; refer to Template SFO
CCTV:
Yes
Section 7, and Schedule C.
MID:
--
Ceiling:
AT (SP)
Security/Duress:
--
Ceiling Height:
2740 mm (9'-0")
VTEL:
--
Wall Finish:
GWB (SC)
VA Satellite TV:
--
Wainscot:
--
Notes:
--
Base:
Resilient Sheet Flooring
Floor Finish:
Resilient Sheet Flooring
Slab Depression:
--
CONDITIONING
Sound Protection:
--
Coordinate with SFO; refer to Template SFO
Notes:
--
Section 6.5.
24C (76F)
Dry Bulb Temp Cooling:
LIGHTING
26C (78F)
Coordinate with SFO; refer to Template SFO
Minimum % Outside Air:
15%
Section 6.7, 6.7.1, 6.7.5.
Yes
Noise Criteria:
NC-35
General:
50-100 FC Non-
Steam:
--
Treatment Area
Relative Humidity/Cooling:
50%
30 FC Patient
Relative Humidity/Heating:
30%
Treatment Area
Minimum Air Changes/Hr.:
10
Special:
Yes
Room Pressure:
Negative
Notes:
1. Wall mounted
AC Load-Equipment:
6 W/SF
fluorescent
AC Load-Lighting:
1.6 W/SF
direct/indirect fixture
Number of People:
8
with acrylic prismatic
--
lens. Provide individual
Notes:
Provide capability to
cubicle switches for
maintain 29C
separate control of
(85F) year round.
direct/indirect lamps.
PLUMBING AND MEDICAL GASES
fluorescent light fixture
with acrylic prismatic
Coordinate with SFO; refer to Template SFO
lens.
Section 6.6 and Schedule B
Cold Water:
Yes
POWER
Hot Water:
Yes
Coordinate with SFO; refer to Template SFO
Laboratory Air:
--
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
Laboratory Vacuum:
--
Sanitary Drain:
Yes
General:
Yes
Reagent grade Water:
--
Emergency:
--
Medical Air:
Yes
Notes:
--
Medical Vacuum:
Yes
Oxygen:
Yes
COMMUNICATION/SPECIAL SYSTEMS
Notes:
--
Coordinate with SFO; refer to Template SFO
Sections 6.7.8, 6.7.9, and Schedule B.
Data:
Yes
Telephone:
Yes
Intercom:
Yes
Nurse Call:
--
Public Address:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
3-2.3