JULY 2005
Design Standards
Aerosolized Pentamidine Procedure Room
ARCHITECTURAL
Coordinate with SFO; refer to Template SFO
CONDITIONING
Section 7, and Schedule C.
Coordinate with SFO; refer to Template SFO
Ceiling:
GWB
Section 6.5.
Ceiling Height:
2740 mm (9'-0")
22C (73F)
Dry Bulb Temp Cooling:
Wall Finish:
Painted GWB
26C (78F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
Resilient Base
Yes
Floor Finish:
Noise Criteria:
NC-35
Slab Depression:
--
Steam:
--
Sound Protection:
STC 40
Relative Humidity/Cooling:
50%
Notes:
--
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
10
LIGHTING
Room Pressure:
Negative
Coordinate with SFO; refer to Template SFO
AC Load-Equipment:
3 W/SF
Section 6.7, 6.7.1, 6.7.5.
AC Load-Lighting:
2 W/SF
Number of People:
3
General:
50-100 FC
--
Special:
--
Notes:
--
Notes:
fluorescent fixture with
PLUMBING AND MEDICAL GASES
acrylic prismatic lens.
Coordinate with SFO; refer to Template SFO
POWER
Section 6.6 and Schedule B
Coordinate with SFO; refer to Template SFO
Cold Water:
Yes
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
Hot Water:
Yes
Laboratory Air:
--
General:
Yes
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
Yes
Notes:
--
Reagent grade Water:
--
Medical Air:
Yes
COMMUNICATION/SPECIAL SYSTEMS
Medical Vacuum:
--
Coordinate with SFO; refer to Template SFO
Oxygen:
--
Sections 6.7.8, 6.7.9, and Schedule B.
Notes:
--
Data:
--
Telephone:
Yes
Intercom:
--
Nurse Call:
--
Public Address:
--
Radio/Entertainment: --
MATV:
--
CCTV:
--
MID:
--
Security/Duress:
--
VTEL:
--
VA Satellite TV:
--
Notes:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
3-1.3