JULY 2005
Design Standards
Chemotherapy Agent Preparation Room
Public Address:
--
ARCHITECTURAL
Radio/Entertainment:
--
Coordinate with SFO; refer to Template SFO
MATV:
--
Section 7, and Schedule C.
CCTV:
--
Ceiling:
GWB
MID:
--
Ceiling Height:
2740 mm (9'-0")
Security/Duress:
--
Wall Finish:
Painted GWB
VTEL:
--
Wainscot:
--
VA Satellite TV:
--
Base:
Resilient Sheet Flooring
Notes:
--
Floor Finish:
Resilient Sheet Flooring
Slab Depression:
--
Sound Protection:
--
CONDITIONING
Notes:
--
Coordinate with SFO; refer to Template SFO
Section 6.5.
LIGHTING
26C (78F)
Dry Bulb Temp Cooling:
22C (72F)
Coordinate with SFO; refer to Template SFO
Section 6.7, 6.7.1, 6.7.5.
Minimum % Outside Air:
Yes
General:
70 FC
Noise Criteria:
NC-40
Special:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
fluorescent light fixture
Relative Humidity/Heating:
30%
with acrylic prismatic
Minimum Air Changes/Hr.:
12
lens.
Room Pressure:
Negative
AC Load-Equipment:
6 W/SF
POWER
AC Load-Lighting:
1.6 W/SF
Coordinate with SFO; refer to Template SFO
Number of People:
6
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
Biological Safety
Cabinet Exhaust
General:
Yes
Notes:
--
Emergency:
Yes
Notes:
1. Junction box/wiring
PLUMBING AND MEDICAL GASES
device for refrigerator.
Connection
Coordinate with SFO; refer to Template SFO
requirements per
Section 6.6 and Schedule B
manufacturer. Connect
Cold Water:
Yes
to emergency system
Hot Water:
Yes
critical power source.
Laboratory Air:
Yes
2. Junction box/wiring
Laboratory Vacuum:
Yes
Sanitary Drain:
safety cabinet.
Reagent grade Water:
--
Connection
Medical Air:
--
requirements per
Medical Vacuum:
--
manufacturer.
Oxygen:
--
Notes:
Provide one natural
COMMUNICATION/SPECIAL SYSTEMS
gas outlet. All
Coordinate with SFO; refer to Template SFO
outlets on left side
Sections 6.7.8, 6.7.9, and Schedule B.
Cabinet.
Data:
Yes
Telephone:
Yes
Intercom:
Yes
Nurse Call:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
3-3.3