June 2006
Medical Center B
VAHBS Data Sheet
Functional Area: 1.5 M BGSF
Stories: 4
Basement: Yes
Subbasement: No
Interstitial Area: 1.0 M
Levels: 5
Construction: Structural Frame: Cast in Place Concrete Walk-on Platform: Gyp Concrete
form board
Service Module Information
Functional Area
Typical Gross Floor
Service Bay
Typical Dimensions
Type
Area per Module
Location
Structural Grid
Floor to Floor
(SF)
Clinical
18,000 to 20,000
External/Internal
22'-6" x 22'-6"
18'-8"
Nursing Units
10,000 to 12,000
External/Internal
22'-6" x 22'-6"
18'-8"
Typical Service Zone Strategy
Typical Subzone Dimensions
S-1
4 1/2"
S-2
24"
S-3
44"
S-4
16"
S-5
11"
Subtotal S-1 through S-6 Subzones = 8'-7 "
S-6
4"
S-7
12 " w/ 9'-0" Clg.
S-3 Subzone Channels--90'-0" Bay
A
U
P
H
H
H
H
U
U
P
U
U
U
A
4'-0"
9'-4"
6'-4"
6'-4"
6'-4"
6'-4"
6'-4"
6'-4"
6'-4"
6'-4"
6'-4"
6'-4"
9'-4"
4'-0"
S-4 Subzone Channels--45'-0" Bay
E
A
H
P
A
E
A
E
A
H
P
A
E
1'-5"
2'-0"
11'-0"
3'-0"
2'-0"
1'-5"
2'-0"
1'-5"
2'-0"
16'-0"
3'-0"
2'-0"
1'-5"
A=Access E=Electrical H=Mechanical P=Plumbing U=Unassigned