Equipment Location
On Grade
6 m (20 ft.)
9 m (30 ft.)
Floor Span
Floor Span
Equipment
Base
Isol
Min.
Base
Isol
Min.
Base
Isol
Min
Type
Type
Defl
Type
Type
Defl
Type
Type
Dfl
20 kW t 75 kW
I
N
7.6
I
N
43
I
S
63
Over 75 kW
I
N
7.6
I
N
63
I
S
89
EQUIPMENT LOCATION
12 m (40 ft.)
15 m (50 ft.)
Floor Span
Floor Span
EQUIPMENT
Base
Isol
Min.
Base
Isol
Min.
Type
Type
Defl
Type
Type
Defl
Up to 1200 W
--
D,L,W
--
--
D,L,W
--
Over 1200 W
500-750 RPM
--
S
63
--
S
89
Over 750 RPM
--
S
63
--
S
89
PUMPS
Closed Coupled
Up to 1200 W
--
D,L,W
--
--
D,L,W
--
Over 1200 W
I
S
43
I
S
43
Base Mounted
Up to 7500 W
--
D,L,W
--
--
D,L,W
--
10 kW to 30 kW
I
S
43
I
S
43
Over 30 kW
I
S
63
I
S
63
DIESEL ENGINES
Up to 19 kW
I
S
63
I
S
63
20 kW to 75 kW
I
S
89
I
S
89
Over 75 kW
I
S
114
I
S
114
Notes:
1.
For suspended floors lighter than 100 mm (4 inch) concrete, select
deflection requirement from next higher span.
2.
If equipment is located in a building separated from building
housing patients, isolator pads are not required.
3.
Direct bolt fire pumps to concrete base. Provide pads (D) for
domestic water booster pump package.
4.
This chart applies to non-seismic areas. If in VA Seismic Area A
or B, substitute DS for D, and SS for S.
31